OPERATION OF DEHUMDIFIER

  • PROCEDURE:
  • STARTING PROCEDURE :
  • Ensure that AHU runs before Switching ON Dehumidifier.
  • Operate the AHU as per the SOP.
  • Ensure that Process air & Reactivation air Dampers of the dehumidifier are in open condition.
  • Ensure the Inlet Valve and Outlet Valve of Steam Coil are in open Condition, and Bypass valve is in closed position.
  • Ensure that Steam Pressure is of 6±1kg/cm2.Switch ON the main MCB.
  • Select the Auto mode to operate automatically and Manual mode to operate the system in manual mode.
  • Ensure the set parameters of the dehumidifier shall yield desired Rh.
  • Switch ON the ON/OFF switch.
  • Ensure the set parameters of dehumidifier Safety thermostat should be 160°C, cool down thermostat should be 70°C and operation thermostat should be in the range of 100°C -140°C.If Dehumidifier runs continuously run, put ‘RC’, in ON time of log sheet.
  •  STOPPING PROCEDURE:
  • Switch OFF the ON/OFF switch.
  • Switch OFF the MCB.
  • Close the process air and reactivate air dampers after switching off the dehumidifier.
  • If the Dehumidifier runs continuously, put ‘RC’ in OFF time Column of log sheet.
  • Whenever performed preventive maintenance activity and filter cleaning activity the same shall be recorded in the remarks column of Annexure-I.

Click the link to download word file copy of this document:
https://pharmaguidehub.com/product/operation-of-dehumdifier/

  • REFERENCES:
  •   Not Applicable
  • ANNEXURES: 
ANNEXURE No.TITLE OF ANNEXURE
Annexure-IDehumidifier Log Sheet
  • ENCLOSURES: SOP Training Record.
  • DISTRIBUTION:
  • Controlled Copy No. 01                     Head Quality Assurance
  • Controlled Copy No. 02                 Head-Engineering
  • Master Copy                           Quality Assurance Department
  • ABBREVIATIONS:
  • SOP     :      Standard Operating Procedure
  • AHU    :      Air Handling Unit.
  • MCB      :    Main Circuit Breaker
  • REVISION HISTORY:
  •    CHANGE HISTORY LOG
Revision No.Details of ChangesReason for ChangeEffective Date
00New SOPNot ApplicableTo be written manual

Annexure-I
DEHUMIDIFIER LOG SHEET

DEHUMIDIFIER LOG SHEET

Click the link to download word file copy of this document:
https://pharmaguidehub.com/product/operation-of-dehumdifier/

Share this article
Shareable URL
Prev Post

CALIBRATION OF ALLIANCE HPLC WITH EMPOWER SOFTWARE FOR PDA AND UV DETECTOR

Next Post

OPERATION OF COOLING TOWER

Leave a Reply

Your email address will not be published. Required fields are marked *

Read next

Discover more from PharmaGuideHub

Subscribe now to keep reading and get access to the full archive.

Continue reading