OPERATING PROCEDURE OF THE 2000 KVA TRANSFORMER

  • OBJECTIVE:

To lay down a procedure for operation of 2000 KVA Transformer.

  • SCOPE:

This SOP is applicable for operation of 2000 KVA Transformer at {Company Name} {Company Location}.

  • RESPONSIBILITY:
  • Technical Assistant – Engineering is responsible to operate the equipment as per the SOP.
  • Head Engineering / In charge – is responsible to ensure the compliance as per the SOP.
  • ACCOUNTABILITY:

Engineering Head

Head Quality Assurance

  • PROCEDURE:
  • Ensure the HT outgoing VCB should be in open condition at the HT panel.
  • Check and ensure the oil level in the Transformer and OLTC up to the mark.
  • Ensure all radiator valves are in open position.
  • Check and ensure for no oil leakages at all the gaskets.
  • Check and ensure the silica gel colour in the breather for sky blue and oil level in the bottom cup up to the mark.
  • Check and ensure for no tools laying on the transformer.
  • Check and ensure transformer for proper neutral & body earthing.
  • Check and reset if any alarms in the RTCC panel.
  • Release the emergency push button at OLTC panel.
  • Close the HT outgoing VCB at the HT panel and observe the LT voltages at the PCC panel.
  • REFERENCES:

  Not Applicable

  • ANNEXURES: 

  Not Applicable

ENCLOSURES: SOP Training Record.

  • DISTRIBUTION:
  • Controlled Copy No. 01                     Head Quality Assurance
  • Controlled Copy No. 02                 Head-Engineering
  • Master Copy                           Quality Assurance Department
  • ABBREVIATIONS:

OLTC      :      On Load Tap Changer

RTCC      :       Remote Tap changer cubical

VCB   :      Vacuum Circuit Breaker

HT           :       High Tension

LT           :       Low Tension

PCC   :      Power Control Centre

KVA        :       Kilo Volt Ampere

  • REVISION HISTORY:
                                                             CHANGE HISTORY LOG
Revision No.Details of Changes Reason for ChangeEffective Date
00New SOPNot ApplicableTo be written manual
Share this article
Shareable URL
Prev Post

PASSIVATION OF STORAGE & DISTRIBUTION PURIFIED WATER SYSTEM

Next Post

PROCEDURE FOR OPERATION OF UN-INTERRUPTIBLE POWER SUPPLY – 40 KVA

Leave a Reply

Your email address will not be published. Required fields are marked *

Read next

Discover more from PharmaGuideHub

Subscribe now to keep reading and get access to the full archive.

Continue reading