Your Compass for Pharma Success

OPERATING PROCEDURE OF WATER COOLED CHILLER

  • OBJECTIVE:

To lay down procedure for the operation of Water Cooled Chiller.

  • SCOPE:

This SOP is applicable for the operation of Water Cooled Chiller at {Company Name} {Company Location}.

  • RESPONSIBILITY:
  • Technical Assistant – Engineering is responsible for operating the equipment as per the SOP.
  • HOD/Executive – Engineering is ensure the compliance as per SOP.
  • ACCOUNTABILITY:

Engineering Head

Head Quality Assurance

  • PROCEDURE:
  • Precautions:
  • Check the level of soft water in the overhead tank, it should be 3/4th or above, if needed fill with soft water.
  • Check the cooling tower water level which should be above half level.
  • Ensure that the suction and delivery valves of chilled water circulation pumps and cooling water pump are open.
  • Ensure cooling towers and chilled water tank make-up water line valves are in open position.
  • Ensure condenser and evaporator in & outlet lines valves are in open position
  • Ensure power supply to panel.Check and ensure the oil level as per the mark given on the view glass.
  • PRE START UP
  • Switch on the input power supply of the chiller.
  • Start the cooling water pumps and related cooling tower fans.
  • Start the chilled water circulation pumps one by one based on plant load.
  • Check and ensure no air lock occurred in the chilled water distribution loop
  • STARTING PROCEDURE
  • Before starting the unit, ensure that all AHU’s are in OFF condition, but valves should be in OPEN condition.
  • Any set points which are desired to be changed may be programmed.
  • All Control Center set points should be programmed before the chiller is started.
  • Maintain the required inlet chilled water pressure. If the flow rate is less than minimum rated flow (3 kg/cm2), the flow switch will be tripped off the system.
  • After getting the flow press and then touch local ON button in MMI and then start the chiller.
  • When the chilled water temperature reaches 6.5ºC, and then starts the AHU’s.
  • Set chilled water outlet temperaure NLT 5℃
  • Every two hours note down the readings as per enclosed Annexure-I.
  • STOPPING PROCEDURE:
  • Press the and then touch STOP button and then stop the chiller.After 1 to 2 minutes the system will be shut down completely.Switch off the chiller pumps and cooling tower pumps.
  • Switch off the cooling tower fans.
  • REFERENCES:

  Not Applicable

  • ANNEXURES: 
  ANNEXURE No.TITLE OF ANNEXURE
Annexure-IWater Cooled Chiller Log Sheet

ENCLOSURES: SOP Training Record.

  • DISTRIBUTION:
  • Controlled Copy No. 01                     Head Quality Assurance
  • Controlled Copy No. 02                 Head-Engineering
  • Master Copy                           Quality Assurance Department
  • ABBREVIATIONS:

AHU    :    Air Handling Units.

MMI     :     Man, Machine Interface

  • REVISION HISTORY:
                                                             CHANGE HISTORY LOG
Revision No.Details of Changes Reason for ChangeEffective Date
00New SOPNot ApplicableTo be written manual

ANNEXURE-I
WATER COOLED CHILLER LOG SHEET

WATER COOLED CHILLER LOG SHEET
Share this article
Shareable URL
Prev Post

OPERATION OF AIR COMPRESSOR AND AIR DRYER

Next Post

OPERATING PROCEDURE OF DG SET

Leave a Reply

Your email address will not be published. Required fields are marked *

Read next

Discover more from PharmaGuideHub

Subscribe now to keep reading and get access to the full archive.

Continue reading