AHU PARAMETER MONITORING

AHU PARAMETER MONITORING
AHU PARAMETER MONITORING
  • OBJECTIVE:

To lay down a procedure for AHU Parameter monitoring.

  • SCOPE:

This SOP is applicable for AHU Parameter monitoring at {Company Name} {Company Location}.

  • RESPONSIBILITY:
  • Technical Assistant – Engineering is responsible to perform the activity as per the SOP.
  • Manager / Executive – Engineering shall ensure compliance as per SOP.
  • ACCOUNTABILITY:

Engineering Head

Head Quality Assurance

  • PROCEDURE:
  • Switch ON the AHU as per the respective SOP.
  • Measure the differential pressure across the filters (10, 5 & 0.3 microns) by using Calibrated digital manometer or magnehelic gauge.
  • Whenever differential pressure of filters exceeds the specified alert limits, clean the filter as per the SOP
  • After cleaning the filters ensure that clean filters differential pressure is within the limits and enter filter cleaning details in ‘Filter cleaning log’.
  • Check the chilled water/hot water inlet and outlet pressure and check the functioning of modulating valves.
  • If the inlet and outlet pressure difference is more than 1 kg/cm2, clean the strainer.
  • Check the chilled water/hot water inlet and outlet temperature.
  • Chilled water inlet temperature should be in the range of 5 – 9°C and outlet temperature should be in the range of 11 – 15°C. Hot water inlet temperature should be in the range of 40 – 60°C and outlet temperature should be in the range of 20 – 40°C.
  • AHU Parameters shall be checked once in 15±3 days for all process areas and 30 ±1 day for all other Non process areas, and recorded in Annexure-I.

Click the link to download word file copy of this document:
https://pharmaguidehub.com/product/ahu-parameter-monitoring/

  • REFERENCES:

  Not Applicable

  • ANNEXURES: 
ANNEXURE No.TITLE OF ANNEXURE
Annexure-IAHU Parameter Monitoring checklist

ENCLOSURES: SOP Training Record.

  • DISTRIBUTION:
  • Controlled Copy No. 01                     Head Quality Assurance
  • Controlled Copy No. 02                 Head-Engineering
  • Master Copy                           Quality Assurance Department
  • ABBREVIATIONS:

SOP                               :          Standard Operating Procedure

kg/cm2                          :          Kilograms per square centimeters

  • REVISION HISTORY:
                                                             CHANGE HISTORY LOG
Revision No.Details of Changes Reason for ChangeEffective Date
00New SOPNot ApplicableTo be written manual

ANNEXURE-I
AHU PARAMETER MONITORING CHECKLIST

AHU PARAMETER MONITORING CHECKLIST

Click the link to download word file copy of this document:
https://pharmaguidehub.com/product/ahu-parameter-monitoring/

Share this article
Shareable URL
Prev Post

REPLACEMENT OF VENT FILTERS FOR PURIFIED WATER STORAGE TANK AND REVERSE OSMOSIS PRODUCT WATER STORAGE TANK

Next Post

PREVENTIVE MAINTENANCE PROGRAMME

Leave a Reply

Your email address will not be published. Required fields are marked *

Read next

Discover more from PharmaGuideHub

Subscribe now to keep reading and get access to the full archive.

Continue reading