  • OBJECTIVE:

To lay down procedure for the operation of  DG set.

  • SCOPE:

This SOP is applicable for the operation of  DG set at {Company Name} {Company Location}.

  • RESPONSIBILITY:
  • Technical Assistant – Engineering is responsible for perform the activity as per the SOP.
  • HOD/Executive – Engineering is ensure the compliance as per SOP.
  • ACCOUNTABILITY:

Engineering Head

Head Quality Assurance

  • PROCEDURE:
  • Precautions:
  • Check the engine oil level with dip stick oil gauge, if required top up engine oil up to the high level mark.
  • Check the coolant level, if required top up the coolant up to the maximum level.
  • Check and Ensure battery charging system and batteries.
  • Battery voltage should not be less than 24V.
  • Check cooling tower water level, if required top up the water up to the maximum level.
  • STARTING PROCEDURE
  • Release the emergency push button on DG power command control.   
  • Turn Off / Manual / Auto selector switch to Manual position.   
  • Press manual Run / Stop button to start the DG set.   
  • Check and ensure the oil pressure, voltage, and RPM in DG power command control panel.
  • Release the emergency push button in the DG control panel.
  • Close the ACB manually in the DG control panel.
  • Close the DG incomer ACB in the power control centre.
  • Switch ON the CT pump, ID fan in the utility MCC panel.
  • Enter the readings in the DG set running parameters log sheet for every hour.
  • STOPPING PROCEDURE
  • Check and ensure the EB power supply presence & ensure the 3 Phase voltages should be in-between 415 – 420 Volts.
  • Note down the final readings in the DG set running parameters log sheet.
  • Open the DG incomer ACB in the power control centre and close the EB Incomer ACB in the power control centre.
  • Switch ON the CT pump, ID fan in the utility MCC panel.
  • Open the ACB of DG control panel manually and press the emergency push button.
  • Run the DG set for 5 minutes in idle condition.
  • Press manual Run / Stop button in the power command control to stop the DG set.
  • Turn Off / Manual / Auto selector switch to “O” position.Press the emergency push button on DG power command control.
  • Switch OFF the CT pump and ID fan in the Utility MCC panel.

    Click the link to download word file copy of this document:
    https://pharmaguidehub.com/product/operating-procedure-of-dg-set/

    • REFERENCES:

      Not Applicable

    • ANNEXURES: 
      ANNEXURE No.TITLE OF ANNEXURE
    Annexure-IDG set running parameters log Sheet

    ENCLOSURES: SOP Training Record.

    • DISTRIBUTION:
    • Controlled Copy No. 01                     Head Quality Assurance
    • Controlled Copy No. 02                 Head-Engineering
    • Master Copy                           Quality Assurance Department
    • ABBREVIATIONS:

    DG Set           :          Diesel Generator Set

    KVA               :          Kilo Volt Ampere

    PCC                :          Power Command Control

    RPM               :          Revolutions Per Minute

    ACB               :          Air Circuit Breaker

    CT                  :          Cooling Tower

    ID                   :          Inner Draft

    MCC              :          Motor Control Centre

    EB                  :          Electricity Board

    SOP                :          Standard Operating Procedure

    NA                  :          Not Applicable

    • REVISION HISTORY:
                                                                 CHANGE HISTORY LOG
    Revision No.Details of Changes Reason for ChangeEffective Date
    00New SOPNot ApplicableTo be written manual

    ANNEXURE-I
    DG SET RUNNING PARAMETERS LOG SHEET

    DG SET RUNNING PARAMETERS LOG SHEET

    Click the link to download word file copy of this document:
    https://pharmaguidehub.com/product/operating-procedure-of-dg-set/

    Share this article
    Shareable URL
    Prev Post

    OPERATING PROCEDURE OF WATER COOLED CHILLER

    Next Post

    OPERATING PROCEDURE OF AIR SHOWER

    Leave a Reply

    Your email address will not be published. Required fields are marked *

    Read next

    SOP FOR MOLYBDENUM TEST

    The molybdenum test is a vital analytical procedure used to identify the presence of molybdenum in stainless…
    SOP FOR MOLYBDENUM TEST

    Discover more from PharmaGuideHub

    Subscribe now to keep reading and get access to the full archive.

    Continue reading